Impact of thermal stratification on airborne transmission risk of SARS-CoV-2 in various indoor environments.
Ontology highlight
ABSTRACT: There exist various vertical temperature gradients in different-type buildings. A holistic understanding of the impact of different temperature-stratified indoor environments on infection risk is necessary. In this work, the airborne transmission risk of SARS-CoV-2 in different thermally stratified indoor environments is assessed using our previously developed airborne infection risk model. Results show that the vertical temperature gradients in office building, hospital, classroom, etc. are within the range of -0.34 to 3.26 °C/m. In large space such as coach station, airport terminal, and sport hall, the average temperature gradient ranges within 0.13-2.38 °C/m in occupied zone (0-3 m); in ice rink with special requirements of indoor environment, the temperature gradient is higher than th
SUBMITTER: Liu F
PROVIDER: S-EPMC10166632 | biostudies-literature | 2023 May
REPOSITORIES: biostudies-literature