A Holistic Evaluation of Multivariate Statistical Process Monitoring in a Biological and Membrane Treatment System.


ABSTRACT: Unsupervised process monitoring for fault detection and data cleaning is underdeveloped for municipal wastewater treatment plants (WWTPs) due to the complexity and volume of data produced by sensors, equipment, and control systems. The goal of this work is to extensively test and tune an unsupervised process monitoring method that can promptly identify faults in a full-scale decentralized WWTP prior to significant system changes. Adaptive dynamic principal component analysis (AD-PCA) is a dimension reduction method modified to address autocorrelation and nonstationarity in multivariate processes and is evaluated in this work for its ability to continuously detect drift, shift, and spike faults. For spike faults, univariate drift faults, and multivariate shift faults, implementing AD-PCA on

SUBMITTER: Newhart KB 

PROVIDER: S-EPMC10928711 | biostudies-literature | 2024 Mar