Performance analysis of high voltage disc insulators with different profiles in clean and polluted environments using flashover, withstand voltage tests and finite element analysis.


ABSTRACT: Severe pollution-induced flashovers on insulators present a pressing challenge to power system safety. The frequent failure of high-voltage insulators, particularly in the polluted environments of Pakistan, poses a critical concern. This paper investigates the impact of insulator profile on reducing pollution flashovers, testing two designs as per IEC standard 60383 and simulated using the Finite Element Method in COMSOL Multiphysics®. The test results revealed that deep under-ribs insulators exhibited a 5.008% reduction in flashover voltage, while alternating shed insulators experienced a 3.233% decrease in polluted conditions compared to clean conditions. Notably, under both clean and polluted conditions, alternating shed insulators consistently outperformed deep under-ribs insulators, w

SUBMITTER: Ali A 

PROVIDER: S-EPMC11365998 | biostudies-literature | 2024 Aug