Unknown

Dataset Information

An enhanced protection scheme for power transformers integrating alpha plane analysis.


ABSTRACT: Power transformers play a critical role in electric power systems by facilitating connections between subsystems with different voltage levels. Ensuring their reliable operation and protection against faults is essential for maintaining network stability. Percentage differential (PD) protection, commonly used in transformer protection relays, faces limitations such as dealing with current transformer (CT) saturation during external faults and difficulty in detecting certain fault types. This paper proposes an enhanced transformer protection scheme by integrating the alpha plane (AP) concept, traditionally used in transmission line protection, to improve transformer differential protection. This entails redefining AP restraint and operating zones based on transformer current behavior under

SUBMITTER: Sayed AS 

PROVIDER: S-EPMC11906808 | biostudies-literature | 2025 Mar

REPOSITORIES: biostudies-literature