The Impact of Test Device on the Evaluation Cooling Effect of Radiation-Cooling Materials.


ABSTRACT: Passive radiation cooling technology, as a new zero-energy refrigeration technology method, has received widespread attention in recent years. However, due to differences in the testing devices used by different teams, it becomes difficult to directly compare the cooling performance of the respective prepared materials. This study combines experimental and theoretical methods to explore the impact of testing equipment and sample size on the results of the radiative cooling capacity evaluation. The research results show that when evaluating the cooling performance of materials in thermal insulation chambers, if the sample diameter is equal to or larger than 10 cm, at a sample diameter ≥ 10 cm in insulated chambers, cooling capacity stabilizes at ~25 °C (daytime) and ~28 °C (nighttime), with