Two thermal performance test (TPT) datasets of a single U-tube borehole heat exchanger with inlet setpoint temperatures of 30 °C and 40 °C.
Ontology highlight
ABSTRACT: The presented thermal performance test (TPT) datasets were related to the research article "New perspectives in thermal performance test: Cost-effective apparatus and extended data analysis" (Choi et al., 2018), where a new TPT apparatus was developed by adding a solid-state-relay and a proportional-integral-derivative (PID) controller to a thermal response test apparatus. Using the developed apparatus connected to a 50-m-long vertical ground heat exchanger, two TPTs were conducted for 144 h with inlet setpoint temperatures of 30 °C and 40 °C. The raw data were measured at 5 s intervals and consisted of the inlet, and outlet fluid temperatures, and the flow rate. The attached MATLAB script allows users to easily filter the data at user-specified time intervals. Moreover, the execution of c
SUBMITTER: Choi W
PROVIDER: S-EPMC6169374 | biostudies-literature | 2018 Oct
REPOSITORIES: biostudies-literature