Copper-silver ionization at a US hospital: Interaction of treated drinking water with plumbing materials, aesthetics and other considerations.


ABSTRACT: Tap water sampling and surface analysis of copper pipe/bathroom porcelain were performed to explore the fate of copper and silver during the first nine months of copper-silver ionization (CSI) applied to cold and hot water at a hospital in Cincinnati, Ohio. Ions dosed by CSI into the water at its point of entry to the hospital were inadvertently removed from hot water by a cation-exchange softener in one building (average removal of 72% copper and 51% silver). Copper at the tap was replenished from corrosion of the building's copper pipes but was typically unable to reach 200 μg/L in first-draw and flushed hot and cold water samples. Cold water lines had >20 μg/L silver at most of the taps that were sampled, which further increased after flushing. However, silver plating onto copper pipe s