Experimental study on the control effect of different ventilation systems on fine particles in a simulated hospital ward.


ABSTRACT: In recent years, a large number of respiratory infectious diseases (especially COVID-19) have broken out worldwide. Respiratory infectious viruses may be released in the air, resulting in cross-infection between patients and medical workers. Indoor ventilation systems can be adjusted to affect fine particles containing viruses. This study was aimed at performing a series of experiments to evaluate the ventilation performance and assess the exposure of healthcare workers (HW) to virus-laden particles released by patients in a confined experimental chamber. In a typical ward setting, four categories (top supply and exhaust, side supply and exhaust) were evaluated, encompassing 16 different air distribution patterns. The maximum reduction in the cumulative exposure level for HW was 70.8% in v