Model-based monitoring of diffuser fouling using standard sensors.
Ontology highlight
ABSTRACT: Fouling of fine-pore diffusers can cause substantial aeration energy wastage. It remains challenging to monitor their condition and decide the optimal time for labour-intensive and costly cleaning actions. In this study, we show that data from standard sensors (airflow rate, dissolved oxygen concentration, pressure and airflow valve position), which are fed to simple models, can track the diffuser's condition. Additionally, the parameter estimation of diffuser dynamic wet pressure, oxygen transfer rate, respiration rate and the joint alpha fouling factor (αF) was facilitated by an active fault detection inspired method. The method executes a sequence with piecewise constant valve positions via the control system. As a result, airflow rates in a sequence similar to a staircase are obtained,
SUBMITTER: Samuelsson O
PROVIDER: S-EPMC8473778 | biostudies-literature | 2021 Dec
REPOSITORIES: biostudies-literature
ACCESS DATA