Leakage current characteristics in estimating insulator reliability: experimental investigation and analysis.
Ontology highlight
ABSTRACT: The monitoring of leakage current (LC) and voltage characteristics in transmission line insulators is regarded as a good technique for anticipating the physical state of in-service insulators. In the current work, the temporal and frequency characteristics of LC and voltage under various situations were derived for assessing the health condition of porcelain, glass, and silicone rubber insulators. The contamination severity indicated by soluble deposit density, wetting level (Wt), non-soluble deposit density, and uneven pollution distribution (Pu/PL) were chosen as the environmental factors that impact the insulators. Six criteria were utilized to evaluate the physical state of the insulators, with four of those derived from the LC signal in the time domain, namely, t
SUBMITTER: Salem AA
PROVIDER: S-EPMC9440045 | biostudies-literature | 2022 Sep
REPOSITORIES: biostudies-literature