Unknown

Dataset Information

Assessment of the Effectiveness of Ventilation Controls in Managing Airborne and Surface Lead Levels at a Newly Commissioned Indoor Shooting Range.


ABSTRACT: Lead levels at a new indoor target shooting range were assessed using both personal and environmental air monitoring methods. Surface swabs were collected from representative locations throughout the range prior to, and at the conclusion of, shooting. Personal samples were compared against the current Australian Workplace Exposure Standards with all results exceeding statutory limits. Static environmental samples exceeded the Air National Environmental Protection Measures (NEPM) air quality standard. Surface swabs showed significant increases from pre- to post-shooting with levels exceeding recommended limits. The performance of the mechanical ventilation system was also assessed and airflow levels were below the required rate at all test locations when compared against the values recommen

SUBMITTER: Alcock R 

PROVIDER: S-EPMC9517389 | biostudies-literature | 2022 Sep

REPOSITORIES: biostudies-literature