Full-scale walk-in containerized lithium-ion battery energy storage system fire test data.
Ontology highlight
ABSTRACT: Three installation-level lithium-ion battery (LIB) energy storage system (ESS) tests were conducted to the specifications of the UL 9540A standard test method [1]. Each test included a mocked-up initiating ESS unit rack and two target ESS unit racks installed within a standard size 6.06 m (20 ft) International Organization for Standardization (ISO) container. All tests were conducted with an identical LIB configuration. The initiating unit rack included nine modules (2,430 individual 18650 form factor cells) with a total capacity of 28.9 kWh. The target unit racks were loaded to one-third capacity of the initiating unit with nine partial modules and a total capacity of 9.6 kWh. All cells in the container were charged to 100% state-of-charge and none were electrically connected. Within the